vuoi
o PayPal
tutte le volte che vuoi
The disadvantages of an All air systems are: Ducts installed in ceiling plenums require
additional duct clearance, sometimes reducing ceiling height and/or increasing
building height. In retrofits, these clearances may not be available; Larger floor plans
may be necessary to allow adequate space for vertical shafts (if required for air
distribution). In a retrofit application, shafts may be impractical; In commercial
buildings, air-handling equipment rooms represent non-rentable or non-revenue-
generating spaces; Accessibility to terminal devices, duct-balancing dampers, etc.,
requires close cooperation between architectural, mechanical, and structural
designers; Air balancing, particularly on large systems, can be cumbersome; and
Mechanical failure of a central air-handling component, such as a fan or a cooling-coil
control valve, affects all zones served by that unit.
All Air systems are classified in three categories: Single-duct systems, Dual-duct
systems and Multizone.
Single-duct systems contain the main heating and cooling coils in a series-flow air
path. A common duct distribution
system at a common air temperature
feeds all terminal apparatus. Single-duct
systems can serve single zone or
multizone. The simplest all-air system is
a supply unit serving a single zone.
The unit can be installed either in or
remote from the space it serves, and
may operate with or without distribution ductwork. Ideally, this system responds
completely to the space needs, and well-designed control systems maintain
temperature and humidity closely and efficiently. Single-zone systems often involve
short ductwork with low pressure drop and thus low fan energy, and can be shut down
when not required without affecting operation of adjacent areas, offering further
energy savings. A return or relief fan may be needed, depending on system capacity
and whether 100% outside air is used for cooling as part of an economizer cycle. Relief
fans can be eliminated if over pressurization can be relieved by other means. Single
duct multizone (zonal reheating) is actually a mixed air/water system since the
zone terminals with the reheating coils are feeded with an hydronic circuit. Multiple-
zone reheat is a modification of the single-zone system. It provides (1) zone or space
control for areas of unequal loading, (2) simultaneous heating or cooling of perimeter
areas with different exposures, and (3) close control for temperature, humidity, and
space pressure in process or comfort applications. As the word reheat implies, heat is
added as a secondary simultaneous process to either preconditioned (cooled,
humidified, etc.) primary air or recirculated room air. Relatively small lowpressure
systems place reheat coils in the ductwork at each zone. More complex designs
include high-pressure primary distribution ducts to reduce their size and cost, and
pressure reduction devices to maintain a constant volume for each reheat zone. The
system uses conditioned air from a central unit, generally at a fixed cold-air
temperature that is low enough to meet the maximum cooling load. Thus, all supply
air is always cooled the maximum amount, regardless of the current load. Heat is
added to the airstream in each zone to avoid overcooling that zone, for every zone
except the zone experiencing peak cooling demand. The result is very high energy
use, and therefore use of this system is restricted. However, the supply air
temperature from the unit can be varied, with proper control, to reduce the amount of
reheat required and associated energy consumption. Care must be taken to avoid high
internal humidity when the temperature of air leaving the cooling coil is allowed to rise
during cooling. In cold weather, when a reheat system heats a space with an exterior
exposure, the reheat coil must not only replace the heat lost from the space, but also
must offset the cooling of the supply air (enough cooling to meet the peak load for the
space), further increasing energy consumption. If a constant-volume system is
oversized, reheat cost becomes excessive. In commercial applications, use of a
constant-volume reheat system is generally discouraged in favor of variable-volume or
other systems. Constant-volume reheat systems may continue to be applied in
hospitals, laboratories, and other critical applications where variable airflow may be
detrimental to proper pressure relationships (e.g., for infection control).
Capacity can be controlled by varying the air temperature or volume in fact Single-
duct systems can be classified as constant volume system or variable volume system.
Constant Volume system: While maintaining constant airflow, single-duct constant
volume systems change the supply air temperature in response to the space load. A
VAV system controls temperature in a space by varying the quantity of supply air
rather than varying the supply air temperature. A VAV terminal unit at the zone varies
the quantity of supply air to the space. The supply air temperature is held relatively
constant. Although supply air temperature can be moderately reset depending on the
season, it must always be low enough to meet the cooling load in the most demanding
zone and to maintain appropriate humidity. VAV systems can be applied to interior or
perimeter zones, with common or separate fans, with common or separate air
temperature control, and with or without auxiliary heating devices. The greatest
energy saving associated with VAV occurs at the perimeter zones, where variations in
solar load and outside temperature allow the supply air quantity to be reduced.
Humidity control is a potential problem with VAV systems. If humidity is critical, as in
certain laboratories, process work, etc., constant-volume airflow may be required.
Dual-duct systems contain the main heating and cooling coils in parallel-flow or
series/parallel-flow air paths with either
(1) a separate cold- and warm-air duct
distribution system that blends air at the
terminal apparatus (dual-duct systems),
or (2) a separate supply air duct to each
zone with the supply air blended at the
main unit with mixing dampers
(multizone). In each conditioned zone, air
valve terminals mix warm and cold air in proper proportion to satisfy the space
temperature and pressure control. Dual-duct systems may be designed as constant
volume or variable air volume; a dual-duct, constant-volume system uses more energy
than a single-duct VAV system. As with other VAV systems, certain primary-air
configurations can cause high relative humidity in the space during the cooling
season. Constant Volume: Dual-duct, constant-volume systems using a single supply
fan were common through the mid-1980s, and were used frequently as an alternative
to constant-volume reheat systems. Today, dual-fan, dual-duct are preferred over the
former, based on energy performance. There are two types of dual-duct, single-fan
application: with reheat, and without. Variable Air Volume: Dual-duct VAV systems
blend cold and warm air in various volume combinations. These systems may include
single-duct VAV terminal units connected to the cold-air duct distribution system for
cooling only interior spaces and the cold duct may serve perimeter spaces in sync with
the hot duct. This saves reheat energy for the air for those cooling-only zones because
space temperature control is by varying volume, not supply air temperature, which
may save some fan energy to the extent that the airflow matches the load.
The Multizone system supplies several zones from a single, centrally located air-
handling unit. Different zone requirements are met by mixing cold and warm air
through zone dampers at the air handler in response to zone thermostats. The mixed,
conditioned air is distributed throughout the building by single-zone ducts. The return
air is handled conventionally. The multizone system is similar to the dual-duct system
and has the same potential problem with high humidity levels. This system can
provide a smaller building with the advantages of a dual-duct system, and it uses
packaged equipment, which is less expensive. Packaged equipment is usually limited
to about 12 zones, although built-up systems can include as many zones as can be
physically incorporated in the layout. A multizone system is somewhat more energy-
efficient than a terminal reheat system because not all the air goes through the
cooling coil, which reduces the amount of reheat required. But a multizone system
uses essentially the same fan energy as terminal reheat because the airflow is
constant.
Air-water systems characteristic
The two mediums have partially different and complementary function. The function of
the primary air, treated in the AHU: are zone ventilation with external air; control
relative humidity; In same cases partial coverage of sensible thermal loads, while with
liquid medium (water) through
appropriate terminals – e.g. Fan coils
(inductors) the functions are: control zone
temperature and total or partial coverage
sensible thermal loads. Air-water systems
can be classified as Primary air and 1
hydraulic circuit (hot/cold) fan-coils or
Primary air and 2 hydraulic circuit (hot and cold) fan-coils.
Air systems components
Air outlet components
Room air distribution systems can be classified according to
their primary objective and the method used to accomplish
that objective. The objective of any air distribution system is
to condition and/or ventilate the space for occupants’ thermal
comfort, or to support processes within the space, or both.
Methods used to condition a space can be classified as one of
the following:
Mixed systems have little or no thermal stratification of air within the occupied
and/or process space. Overhead air distribution is an example of this type of
system.
Full thermal stratification systems have little or no mixing of air within the
occupied and/or process space. Thermal displacement ventilation is an example
of this type of system.
Partially mixed systems provide limited mixing of air within the occupied
and/or process space. Most underfloor air distribution designs are examples of
this type of system.
Task/ambient air distribution and/or process control. Examples of
task/ambient systems are personally controlled desk outlets and spot-
conditioning systems.
Emission systems (air distribution terminals) are grids, ceiling diffusers,
Displacement terminals, Induction diffusers feeded with primary air and chw, Fan coils
and Chilled beans
Centralised vs decentralised systems
Decentralised (es. split) have, compared to centralised systems the following
advantages: Lower investment cost, Easier to install (pre-insulated and flexible pipes
for refrigerant trasport), Flexible, often can operate as heat pump too and Easy to
control from the user. Decentralised systems disadvantages: Short operation life (less
than 10 years), Not allow proper IAQ control (scarse filtering, limited humidity control),
Total installed power is higher, Higher electricity consumption (almost no “free<